PRODUCTS |
|
NSI manufactures temperature
sensors including
electric heating elements and distributes automation components
including pressure, transmitters, sensors, process controllers. |
|
| |
| |
Sign up to our newsletter |
| |
| |
| |
| |
|
|
 |
PRODUCTS |
| |
| Sensors / Controllers |
| 1200-1300 Configurable controllers |
 |
- Universal input configurable from faceplate
- Accuracy better than 0.2% f.s. under nominal conditions
- Control output: relay, logic, Triac or continuous
- Hot/cold function with selection of cooling fluid
- 3 alarms with completely configurable function
- Analog retransmission output
- Up to 2 isolated digital inputs with configurable function
- Isolated digital input with configurable function
- Auxiliary input for CT (TA) (50mAac)
- Heater break or probe short-circuit alarm
- Self-tuning, Auto-tuning, Soft-start, bumpless Man/Auto function
- Double set, set ramp, timed output function
- Optically isolated RS485 serial line. Protocol: GEFRAN MODBUS RTU
- Self-diagnosis
- Rapid configuration from PC with Winstrum packet
|
Microprocessor controllers, 48x96 (1/8DIN) format for 1200 and 96x96 (1/4DIN) format for 1300, built with SMT technology.
Complete operator interface, protected by Lexan membrane to guarantee an IP65 faceplate protection level.
Composed of 4 keys, double 4-digit green LED display, 4 red signal LEDs for the 4 relay/logic outputs and 3 additional LEDs with programmable function to signal the instrument's various function states.
The main input for the variable to be controlled is universal, and allows connection of a wide variety of signals: thermocouples, resistance thermometers, thermistors, normalized linear inputs, all with possibility of custom linearization set from the faceplate. Input type is selected entirely from the faceplate and requires no external adapter shunts/dividers.
A second auxiliary analog input from current transformer is available. You can
select one of the two presettable set points, select Manual-Automatic mode, reset
the alarm memory, or enable the hold function by means of the digital input.
The instrument provides up to 4 outputs: relay (5A, 250VAC/30VDC cos f = 1) or logic (24V ± 10% (10Vmin a 20mA)).
An analog output in voltage or in current is also available. The functions of
each output are freely configurable from the faceplate. In addition to the control
and alarm outputs, you can also have outputs that repeat the state of the digital
or retransmission input by process variable, set point, deviation, alarm trip
points and values acquired via serial line.
An additional output (24VDC, 30mA max.) is available to power outside transmitters.
The serial communication option can be in Current Loop or RS485, with MODBUS RTU protocol and maximum speed of 19200 baud (485). The instrument's entire programming procedure is made easier by grouping the parameters in function blocks (CFG for control parameters, Inp for inputs, Out for outputs, etc.).
The instrument can also select the parameters to be displayed based on its hardware configuration, which automatically hides irrelevant parameters.
The instrument is supplied with an "EASY" configuration calling for just a few
parameters (only those pertaining to the model ordered and essential to the controller's
operation). In this way, you just have to set the set point and the alarm, then
launch self-tuning with the specific button.
For even simpler configuration, you can use a PC programming kit consisting of a cable and a guided program for Windows environment (see Technical Data code WINSTRUM). |
| |
|
| |
|
|
|
|
| |
|